ACADEMY ELECTRICAL CONTRACTORS Commercial / Industrial Electrical Construction since 1986

Call 877-SPARKYS
(877-772-7597)

hotel electrical construction

Hotel Electrical Rebuild Step 1 Electrical Construction

 

Hotel Electrical Service Rebuild Step 1 

I’m about to show you some photographs of the Hasbrouck Heights Hilton Hotel in Bergen County NJ main electrical service before and after a catastrophic electrical failure.

Here we’re looking at the main electrical service in the hotel. This is the main switchgear service entrance. These are some of the sub-panels that are also in that main electrical room in the basement of the Hilton Hotel. Some of the fused disconnect switches that were in the main electrical service inside the basement service at the Hilton.

A Call for Commercial Electrical Construction

It was Friday, September 28, 2018 when we received a phone call from the Hasbrouck Heights Hilton Hotel. They had an explosion and fire in the main electrical room in the basement. Seen here is the bus duct failure that was so catastrophic it melted the chassis, feeder cables, and splattered aluminum all over the walls in the main electrical room.

The heat on that steel beam above the bus duct. It was so hot that everything is discolored. Other feeder cables that failed because of the heat that was inside the main electrical room. The grounding electrode conductor melted completely in half because the fault current was so high during this fault.

Again, another section of the bus duct that blew out. The bus inside the main switchgear and the bolts that bolted the bus together, that were made of brass, actually melted in half and the bus bar became unbolted.

More damage above the switchgear where you can see the plastic melted. Another section on the bus duct that blew out. And another grounding electrode conductor picture where you can see it’s completely melted in half.

Mimicking The Feeder Circuits

Hotel Temporary PowerNow we had to mimic the feeder circuits that were in the main electrical room, so we started running temporary distribution circuits out of our temporary switchgear in the room next door from our 208 volt panel. Then we had a step down transformer from 480 to 208 to feed that panel, and that is where we got our temporary circuits that we started running back into the main electrical room. Some circuits, 200, 400, 800 amp circuits, whatever we needed to mimic the circuits that were there.

The feeder cables that went outside to the generator from our 480 volt panel to our 425 KW diesel generator outside.

This is the original PSE&G transformer in its location outside before this failure happened. And now, this is the finished outside of our 15,000 volt switchgear on the right, or 1500 KVA transformer on the left, and our 480 volt distribution where the old PSE&G transformer was so we could reuse the conduits going into the building.

And I’ll explain more in detail about this outdoor switchgear in the next video.